WD600 Thermodynamic Steam Trap


HOW IT WORKS

The thermodynamic trap has cyclic on-off operation with a disk that is pushed open by incoming condensate and closes
tightly when steam tries to escape.

FEATURES

  • High pressure applications up to 600 PSIG
  • Hardened stainless steel seat and disc for extended service life even at high pressure
  • Single trap will operate over the entire pressure range (3.5-600 PSIG)
  • Unaffected by superheated steam
  • Freezeproof when trap is piped in a vertical orientation for complete drainage of condensate
  • Three hole balanced discharge extends life of the seat area
  • Trap will function in any orientation (horizontal preferred)

SAMPLE SPECIFICATION

The steam trap shall be a thermodynamic disc type with all stainless steel construction. Integral seat design and disc to be hardened for long service life. Unit shall be capable of installation in any orientation and self-draining when mounted vertically.

INSTALLATION

Trap can be installed in any position; however, horizontal is preferred. Installation should include isolation valves and a 20 mesh strainer. Do not weld as damage can occur to the seat area.

MAINTENANCE

Dirt is the most common cause of premature failure. For full maintenance details, see Installation and Maintenance Manual.

OPTIONS

An insulation cap is available to reduce cycle rates and steam loss in rain, snow, or cold environments.